Prolink PRO810ES

 

 

 

 

Technical Information :

Volt-Amp : 10000VA
Phase : Single Phase In / Single Phase Out
Isolation Transformer : Optional
Input Voltage Range : 110VAC-300VAC
Input Frequency Range : 46 Hz – 54 Hz or 56-64Hz
Input Power Factor Correction : 0.99
Output Voltage : 208/220/230/240VAC
AC Voltage Regulation (Battery Mode) : ± 1%
Output Frequency Range : 46-54Hz
Output Current Crest Ratio : 3:1
Harmonic Distortion :
Transfer Time : 0ms
Waveform (Battery Mode) : Pure Sinewave
Output Power Factor : 1
AC Mode Efficiency : 94%
Battery Mode Efficiency : 91%
Eco Mode Efficiency : 97%
Battery Type : Sealed Maintenance Free
Numbers of Battery : Qty:20;12V,9 Ah
Typical Recharge Time : 9 Hours Recover to 90% Capacity
Charging Current (max.) : 1A
Charging Voltage : 273.0VDC ±1% per Battery
Indicators : LCD Display:UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
Alarm :
  • Battery Mode:Sounding every 4 seconds
  • Low Battery:Sounding every 2 seconds
  • ,Overload:Sounding twice every second
  • Fault:Continuously sounding
Dimension : 442x190x688
Net Weight : 66kg
Environment :
  • Humidity: 20-90% RH @ 0-40°C (Non-condensing)
  • Noise Level:Less than 58dB @ 1 Meter
  • Regulations: EN 62040-1-1:2003, EN 62040-2:2006,EN 61000-2-2:2002, EN 61000-4
Management : Smart RS-232 / USB/SNMP(optional)