UPS_EATON_9_PX___569f249a20ecd

 

 

 

 

 

 

 

 

 

9PX 11KVA R/T, 6U With Rack Mounting Kit Capacity 11000VA/10000W

 

SPESIFIKASI :

General
Topology On-line double conversion with PFC (Power Factor Correction) system
Configuration Rack/Tower
Part Number 9PX11KiRT31
Rating (VA/Watts) 11000/10000
Dimensions (H x W x D, mm) 440 x 260 x 700
Weight (kg) 88
Warranty 2 years warranty
Rail Kit Included Yes
Electrical Input
Connection
Hardwired – see manual for terminal block layout

Hardwired - example layout only

Input Voltage Range 305V-480V without derating (up to 175V-480V with derating)
Nominal Voltage 380/400/415V
Frequency 50/60 Hz autoselection
Frequency Range 40-70 Hz
Short Circuit Current 150 A
THDI <5%
Electrical Output
Voltages 200/208/220/230/240/250V +/– 1%
Voltage THD < 2%
Output Receptacles
Hardwired – see manual for terminal block layout

Hardwired - example layout only

Overload Capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
Efficiency (Normal Mode) Up to 95% in Online mode, 98% in Hi-Efficiency mode
Output Frequency 50/60 Hz autoselect, frequency converter as standard